Call UsCall Us :

Building products Ignitability Apparatus

Building products Ignitability Apparatus

Product Details:

  • Color white
  • Weight 50 Milligram (mg)
  • Warranty 1 year
  • Supply Ability : 10 Set Per Month
1 USD ($)/Set
X

Price And Quantity

  • 1 USD ($)/Set
  • 1 Set

Product Specifications

  • white
  • 50 Milligram (mg)
  • 1 year

Trade Information

  • SHANGHAI
  • Telegraphic Transfer (T/T), Letter of Credit at Sight (Sight L/C)
  • 10 Set Per Month
  • 1 Months
  • Contact us for information regarding our sample policy
  • PLYWOOD
  • Western Europe, South America, Central America, Asia
  • All India

Product Description

Description:

  • This apparatus is manufactured to conform to ISO 5657.The Apparatus has been designed,
  • principally for testing building materials and composites, but it is capable of testing any 
  • sample of size 165mm — 165mm and up to a maximum of 70mm thick. The Apparatus measures 
  • the ignition characteristics of exposed surfaces of essentially flat materials and 


specimens.

Standards:

  • ISO 5657
  • GB/T 14523
  • Model:  FTech-ISO 5657

Features:

1.The radiation cone is made of 304 stainless steel;

2.All internal fixtures are made of stainless steel;

3.The specimen support frame: thickness 1.5mm,

4.The calibration board is made of ceramic fibre of density (20050)kg/m3, with sides 


measuring 165 mm and of thickness not less than 20 mm.

5.The rated power of the conical heater is 3000W, the heat output is 0-70kw / m2, and the 


resolution is 0.5kw/m2;

6.Thermocouple has automatic cold node compensation.

7.The Medtherm heat flux meter imported from the USA  with a water cooling system. Accuracy 

± 3%, reproducibility deviation 0.5%;

8. Ignition device: automatic ignition.

9.Imported gas flowmeter, control of gas flow precisely

10.Install filter in propane gas path; prevent pollution test gas path system;

11.Equipped with check valve to prevent danger;

12.PLC&touch screen automatic control system;

13.Temperature monitor 0 ƒ ~ 1000 ƒ; control heater temperature resolution ± 2 ℃;

14.Nominal range of balance 5000g, accuracy 0.1g;

15.The test data is automatically recorded and automatically saved;

16.The exaust hood is optional.


TESTECH

* Tips on getting accurate quotes. Please include product name, order quantity, usage, special requests if any in your inquiry.