Vertical Tray Fire Test Apparatus

Vertical Tray Fire Test Apparatus

Product Details:

  • Weight 1000 Kilograms (kg)
  • Warranty 1 YEAR
  • Supply Ability : 10 , , Set Per Year
X

Price And Quantity

  • 1 , , Set

Product Specifications

  • 1 YEAR
  • 1000 Kilograms (kg)

Trade Information

  • SHANGHAI
  • Letter of Credit at Sight (Sight L/C), Telegraphic Transfer (T/T)
  • 10 , , Set Per Year
  • 1 Months
  • Contact us for information regarding our sample policy
  • PLYWOOD
  • Western Europe, Asia, South America, Africa, Central America
  • All India

Product Description

DescriptionThis apparatus is used to assess single or bunched cables under defined conditions inhibit the spread of flame apparatus ability to meet UL 1685, IEEE 383 and IEEE 1202's testing requirements. UL flame contact test is a vertical flame test stand, when the cable is subjected to shock and burning fire source, the cable damage height and decided to test the value of smoke emission. We meet the UL testing procedures cable is accepted this device can be used to evaluate the assessment of single cable or multicore cable flame spread situation. In this device can also increase gas analysis HRR (heat release rate), smoke density and other means for analyzing the test material.
Model:FTech-UL1685
Standard: Ã¢â‚¬Â¢ UL1685
• IEEE 1202
• IEEE 383 
 Main Features
1, The test box size is 2,600 (W) x 2,600 (D) x 3,100 (H) mm, the volume is 20.28m3, internal area is 6.76m2.
2, The internal toolings are all made of stainless steel;
3, The combustion test box structure with a smoke discharge hole, there are the fresh air intake;
4, The test room walls made of concrete bricks or refractory bricks. Walls have observation window;
5, The test room containing an access gate made from steel material;
6, Two-way differential pressure sensor measuring flue gas flow rate; and import pressure sensors, pressure precision 0.025pa;
7, K-type thermocouple (Inconel) detects the temperature of the flue;
8, Cable bracket size:(300mmx76mmx2400mm);
9, The burner is formed by the ribbon propane torch and inport wick;
10, Propane flow meter: at standard temperature and pressure (20 ° C, 101 kPa) at (220 ± 8 cm3 / s);
11, Air flow meter: at standard temperature and pressure (20 ° C, 101 kPa) at (1280 ± 80 cm3 / s);
12, Thermocouple and bi-directional wind speed, which installed in the exhaust pipe, can measure exhaust temperature and gas flow rate;
13, Tray size is 305 (length) × 76 (width) × 2438 (height) mm, ladders horizontal width of 25 ± 6mm, spanning a 229mm;
14, Ribbon propane burner with a mixer Ventury, which meet IEC60332-3;
15, Using the data acquisition board, accurately capture and measure the internal component temperatures and burner flame temperature;
16, Solenoid valve and ignition by button on the control panel manual control, emergency situations can turn off the power to the instrument (not including PC power supply)